Maintaining UPS efficiency when the load size diminishes

Kohler Uninterruptible Power News and PR from Kohler Uninterruptible Power - Published 30 August 2017 Modular UPS technology, as implemented in systems such as UPSL’s PowerWAVE 9500DPA, is now being exploited in a smart solution that maintains UPS efficiency even when the UPS load is severely reduced.
Loads in a converged or virtualised data centre environment can drop rapidly if servers are switched off-line in response to a reduced user demand. In other environments, the load may simply be lower than expected, or the contingency allowance may have been set too high. In any case, an unexpectedly low load can cause the upstream uninterruptible power supply (UPS) to operate significantly under capacity; a mode that can reduce its energy efficiency.

Xtra VFI mode, available on the PowerWAVE 9500DPA, solves this problem. The UPS is implemented in one to six racks, each containing up to five 100 kW modules. When enabled, Xtra VFI automatically adjusts the number of active modules to match the load requirement. Any that are not needed are switched to standby mode while remaining in a state of readiness, primed to transfer to active mode instantly if the load increases. The efficiency improvements achieved by this technique are especially significant if the load drops below 25% of the UPS systemÂ’s full capacity. An added benefit of Xtra VFI is that it rotates modules between active and standby, which extends the UPSÂ’s service life.

If the actual load drops to 400 kW, the number of active modules will be reduced to four. This gives the UPS an active capacity of 400 kW, and a standby capacity of 600 kW.

The active modules all operate in double conversion mode, and share the load equally. The passive modules are in standby mode, with their inverters switched off, ready to transfer to active double conversion operation when the load increases.

This scaling of the active module capacity to track the load size maximises UPS efficiency. The system calculates the optimal capacity value for maximum efficiency, while allowing for the desired redundancy. The redundancy level for active capacity and the highest expected load step can be configured by the user to guarantee the highest protection level.

Xtra VFI is de-activated automatically if the mains fails or generates an alarm; all modules switch to ‘active’ status.

UPSs running well below their rated load are frequently found in data centres, especially those where the load can change rapidly. Xtra VFI, together with modular UPS technology, eliminates this overcapacity. The result is improved energy efficiency, especially if the load has dropped to 25% or less of the UPSÂ’s full capacity. Additionally, UPS service life is extended and aging is stabilised as Xtra VFI rotates modules between active and standby modes.



Modular UPS technology is now being exploited in a smart solution that maintains UPS efficiency

Other announcements from Kohler Uninterruptible Power

  • Understanding your UPS battery’s amp-hour rating

    If you’re specifying a UPS system, then it’s absolutely essential that you truly understand its battery autonomy; for how long will it support the load if the AC supplies fail?

    14 May 2018

  • Keeping UPS availability high

    When data centre operators invest in UPS systems, it’s for one purpose only; to maximise power availability for their facility’s ICT equipment.

    14 May 2018

  • Future trends for UPSs

    What does the future hold for UPS technologies and systems? We asked Alan Luscombe, Director at UPSL, for his views, as summarised below.

    02 Nov 2017

  • UPS, heal thyself

    UPSs exist solely to deliver clean, uninterrupted power to their critical load – but their ability to do so is entirely bounded by their resilience to failure of their own components or subsystems.

    31 Aug 2017

  • Is it time to consider Lithium-ion batteries?

    Why hasn’t the industry adopted lithium-ion solutions with greater enthusiasm, and is this likely to change? We can answer these by looking at factors relating to both lead-acid and lithium-ion bat.

    30 Aug 2017

  • How UPS efficiency can contribute to data centre PUE

    Improving UPS efficiency can help to better data centre PUE performance. The article discusses the options for this available to UPS operators who invest in the right, transformerless technology UPSs.

    30 Aug 2017

  • The Internet of Things, data centres, and UPSs

    The Internet of Things (IoT) is gaining traction at an accelerating pace; Gartner has predicted 26 billion connected devices by 2020, while others are calling even higher numbers.

    30 Aug 2017

  • Director's Blog: So just what exactly is a UPS?

    This blog written by Alan Luscombe, UPS Ltd Director, explains what a UPS is, as well as putting the various risks averted by UPS systems into perspective.

    03 Aug 2015

  • Choosing a generator for data centre power protection

    UPS generators are no longer just a backup plan. Today, they are considered a vital component of a company’s power protection policy, as sizing UPS batteries for protracted power blackouts is simply uneconomic and impractical. In choosing a generator for a data centre or other critical IT load application, a number of factors must be considered. These include the generator’s key components, environmental issues and the qualifications of the suppliers as well as compatibility with the UPS to be supported. In this article, Alan Luscombe, director at Uninterruptible Power Supplies Ltd., a Kohler company, discusses how generators work with UPSs, and the factors you must consider when choosing a generator as part of your power protection policy.

    23 Jul 2015